| MODEL |
GB07 |
GB110 |
| POWER RATING |
PV Input (kWp) STC |
9kWp Max. STC |
12KWp Max. STC |
| AC Output(kVA/kW) |
7.5kW |
10kW |
| SOLAR CONTROLLER & AC CHARGER |
PV Max.Open Circuit Voltage(Voc)/ Vmp at STC |
150Vdc / (120-500Vdc option) |
| PV MPPT Voltage Range/Vmp at STC |
64-145Vdc / (290-500Vdc option) |
| Max PV Charging Current (A) |
3MPPTs 180A 12Strings (Mppt 60A 4Strings) |
| Max AC Charging Current (A) |
176-275 Vac 50Hz 180A |
| BATTERY |
Normal Voltage/Output Voltage(Vdc) |
48Vdc/ Battery Voltage |
| Voltage Range(Vdc) |
42 – 62 Vdc |
| Max.Battery discharge(A) |
230A(90A*3) |
| Low Voltage Alarm (Vdc) |
44.0 – 47.2Vdc |
| High Voltage Alarm (Vdc) |
60Vdc |
| Battery type |
Lead Acid / VRLA / Lithium |
| AC OUTPUT |
Output Voltage (Vac) |
220/230/240Vac (L-N) |
| Output Regulation |
+/-1% |
| Phase |
1 Phase 2Wire + PE |
| Output Frequency (Hz) |
50/60Hz +/- 0.1% |
| Output Current (A) / THDi |
34A / <5% |
45.45A / <5% |
| Total Harmonic Distortion(THDv) |
Grid Tied/Grid charging mode <3%, Backup mode <3% |
| Voltage Response time (0 – 100%) |
20ms |
| Power Factor |
Grid Tied & Grid charger >0.99 defualt @ 0.8 Leading to 0.8 Lagging |
| Overload Capability |
110% for 30minutes, 125% for 1 minute, 150% for 30 seconds |
| Maximum Surge Current |
200% for 10 seconds |
| Grid Tied/Backup Transfer Time |
2-4ms |
| Output Wave Form |
Pure Sine Wave |
| Standby Power Consumption |
<2W |
| PROTECTION |
System Protection |
Revarse Polarity, Anti-islanding, Ground Fault Monitoring, AC/DC Under/Over voltage, Over Charge/Over discharge, Overload, Over current, Over Temperature, SPD and AC Short circuit |
| EFFICIENCY |
Max.Inverter Efficiency |
≥95% |
| Max.Charger Efficiency |
≥98% |
| AC INPUT FORM GRID LINE OR GENERATOR |
Maximum AC Current (A) |
80A |
| AC Voltage (Vac) |
220/230/240 (L-N) |
| Voltage Range |
(176-275 Vac) |
| Frequency(Hz) |
50/60 Hz +/-3% |
| DISPLAY (REAL TIME) |
LED indication Inverter/Solar Charger LCD Real time Inverter/ Solar Chager LCD External Inverter/ Solar Chager |
AC, Iverter, Charge(CHG.), Fault, Output voltage/Current/Frequency, Input voltage/Current PV Voltage/Current, Watt Battery voltage,Charge/Discharge Voltage, Current, SOC, SOH, Status, Alarm, Max charge/Discharge current, Load,VA,Watt, Daily kWh, Total kWh |
| ALARM |
System Alarm |
Low battery, Overload, High Temperature and Short circuit |
| COOLING |
|
Nature Cooling, Automatic cooling fan |
| INTERFACE |
Communication and Application Software |
RS232/ RS485/Canbus, Computer, WiFi and Smart phone (Software monitoring optional) |
| PHYSICAL |
Inverter Type |
Tower |
| Dimension W x H x D (mm.) |
400*840*555 |
| Weight(kg) |
130 |
| ENVIRONMENT |
Operation Temperature |
0 – 50 oC |
| Humidity |
0 – 100% (Non – condensing) |
| Ambient humility |
0 – 100% relative humility (non – condensing) |
| Noise Emission |
Less than 40dB |
| DESING REGULATION |
Standard |
IEC 62040, Accordance to IEEE 929-2000, IEEE 1547-2003, IEC 61727-2004 and IEC 62116-2008 Incorporating with PEA Recommendation, B.E. code 2559 |
| Enclosure |
IP20 or IP65 or IP68 |